工程案例
Projects
Release Time:2018-06-01
View Count:3594
This is an expansion project of coke plant for Guangdong Shaogang Steel, a subsidiary of Baosteel Group. The designed capacity of WWTP is 1440m3/d. The effluent complies with the discharge limit standard GB16171-2012. It achieves the best treatment effect under the discharge limit.

Influent Wastewater Quality:
| Index | Distillation of Ammonia | Desulfurization Liquid Waste | Coke Processing Waste Water | Other Wastewater | 
| pH | 8-11 | 4-11 | 3-8 | 4-9 | 
| COD | ≤4500 | 6000-20000 | 25000 | ≤200 | 
| Volatile Phenols | ≤1000 | ≤500 | 5000 | ≤100 | 
| Cyanide | ≤150 | ≤2000 | ≤100 | ≤10 | 
| Ammonia Nitrogen | ≤250 | ≤1200 | ≤100 | ≤100 | 
| Sulfide | ≤150 | ≤6000 | ≤100 | ≤50 | 
| Oil | ≤300 | ≤500 | ≤1300 | ≤100 | 
| Water Volume | 48 | 2 | 4-6 | 4 | 
Effluent Water Quality:
| COD | <80mg/L | Total Phosphorus | <1mg/L | Petroleum | <2.5mg/L | 
| Volatile Phenols | <0.3mg/L | PAH | <0.05mg/L | Sulfide | <0.5mg/L | 
| Cyanide | <0.2mg/L | BaP | <0.03ug/L | Total Nitrogen | <20mg/L | 
| Ammonia Nitrogen | <0.2mg/L | BOD5 | <20mg/L | Benzene | <0.1mg/L | 
| Suspended Solids | <50mg/L | Chroma | <50mg/L | 
The Process Diagram: